Solar PV Diverter Settings and Schedule

Customise and control how your system uses solar energy. 

  • Cut-in Threshold: The minimum power the PV diverter must be producing before it will start heating the cylinder 0w – 500w. Normally set to 0w. Note: If Tesla Batteries are installed it is recommended to set the cut-in threshold to 100w
  • PV Charge Limit: The maximum hot water level the cylinder can reach when being heated by the PV diverter 10% - 100%. Normally 10%.
  • PV Diverter Target Temperature: The temperature to which the PV diverter can heat the water. This can be higher than the target temperature to optimise solar gain. Off - 60°C if off will be same as target temperature, set to 60°C to optimise solar gain.
  • Target Export Current: The PV diverter will be controlled with the aim of maintaining the export current from the premises at this value 0.0A to -1.0A.

PV Diverter Schedule

  • Use Spare PV to Heat Tank: When enabled, any spare PV energy will be used to heat the cylinder. By disabling this setting, any spare PV energy will be exported to the grid. Note: Mixergy iHP requires a minimum of 250w available and uses the heat pump to heat the cylinder.
  • PV Diverter Start Time: The time at which the PV diverter can start heating the Mixergy cylinder.
  • PV Diverter End Time: The time at which the PV diverter will stop heating the Mixergy cylinder. Note: If the PV Diverter Start Time and PV Diverter End Time settings have been set, the Use spare PV to heat tank setting will be ignored.

Graph Setting

  • Show Clamp Power Graph: If enabled CT Clamp power in will be visible in the Graphs section.