Mk2 Heat Pump Interface DIP switches
This article outlines how to set the DIP switches on the Mk2 HP Interface Unit.
The heat pump interface uses DIP switches to set a resistance that emulates the heat pump’s temperature sensor.
Once set the resistances can be checked by measuring between the COM to HOT or COM to COLD test points next to the large relay, while the unit is electrically isolated.
Note: When using the Heat Pump DHW temperature probe the Cold Dip switches must all be set to the off position.
| Switch number | Mitsubishi | LG | Vaillant | |||
| Hot | Cold | Hot | Cold | Hot | Cold | |
| 1* | On | On | On | On | On | On |
| 2 | Off | On | On | On | On | Off |
| 3 | On | Off | On | Off | On | Off |
| 4 | On | Off | Off | Off | Off | Off |
| 5 | Off | On | On | On | Off | On |
| 6 | Off | On | Off | On | On | On |
| 7 | On | On | On | On | On | Off |
| 8 | On | Off | On | Off | On | On |
| 9 | On | On | On | On | On | On |
| 10 | On | On | On | On | On | On |
| 11 | On | On | On | On | On | On |
| 12 | On | On | On | On | On | On |
| 13** | On | On | On | |||
| 14** | On | On | On | |||
| Total resistance | 1280 | 3600 | 1020 | 3600 | 610 | 1990 |
| Switch number | Hitachi | Nibe | Samsung | |||
| Hot | Cold | Hot | Cold | Hot | Cold | |
| 1* | On | On | On | On | On | On |
| 2 | On | On | Off | Off | Off | On |
| 3 | Off | On | On | Off | On | Off |
| 4 | Off | On | Off | Off | On | On |
| 5 | On | On | Off | On | On | On |
| 6 | On | On | On | On | On | Off |
| 7 | On | On | On | Off | Off | On |
| 8 | Off | On | On | On | Off | Off |
| 9 | On | On | On | On | On | Off |
| 10 | On | Off | On | On | On | Off |
| 11 | On | On | On | On | On | Off |
| 12 | On | On | On | On | Off | On |
| 13** | On | On | Off | |||
| 14** | On | On | On | |||
| Total resistance | ||||||
| Switch number | Daikin High Temp | Daikin Low Temp | PT1000 | |||
| Hot | Cold | Hot | Cold | Hot | Cold | |
| 1* | On | On | On | On | On | On |
| 2 | On | Off | Off | Off | On | On |
| 3 | Off | On | On | Off | On | Off |
| 4 | Off | Off | Off | Off | On | Off |
| 5 | Off | On | On | On | Off | On |
| 6 | On | On | Off | On | Off | Off |
| 7 | On | Off | Off | Off | On | On |
| 8 | Off | Off | Off | On | On | On |
| 9 | On | Off | On | On | On | On |
| 10 | On | Off | Off | Off | On | On |
| 11 | On | On | Off | Off | On | On |
| 12 | On | On | On | Off | On | On |
| 13** | On | On | On | |||
| 14** | On | Off | On | |||
| Total resistance | 4010 | 24990 | 45010 | 291990 | 1230 | 1120 |
| Switch number | Midea | Panasonic | Ecoforest/Viessman | |||
| Hot | Cold | Hot | Cold | Hot | Cold | |
| 1* | On | On | On | On | On | On |
| 2 | Off | On | On | Off | Off | On |
| 3 | Off | On | Off | On | On | On |
| 4 | Off | Off | Off | Off | On | Off |
| 5 | Off | On | Off | Off | On | On |
| 6 | Off | On | On | Off | Off | On |
| 7 | Off | On | On | On | Off | On |
| 8 | On | On | On | On | On | On |
| 9 | Off | Off | On | On | On | Off |
| 10 | On | On | On | On | On | On |
| 11 | On | Off | On | On | On | On |
| 12 | On | On | On | On | On | On |
| 13** | On | On | ||||
| 14** | On | On | ||||
| Total resistance | 10020 | 33000 | 710 | 1480 | 2510 | 7000 |
| Switch number | ATAG | Dimplex | ||||
| Hot | Cold | Hot | Cold | Hot | Cold | |
| 1* | On | On | On | On | ||
| 2 | Off | On | Off | On | ||
| 3 | On | On | Off | On | ||
| 4 | On | Off | On | Off | ||
| 5 | On | On | Off | On | ||
| 6 | Off | On | Off | On | ||
| 7 | Off | On | Off | On | ||
| 8 | On | On | On | On | ||
| 9 | On | Off | On | Off | ||
| 10 | On | On | On | On | ||
| 11 | On | On | On | On | ||
| 12 | On | On | On | On | ||
| 13** | On | On | ||||
| 14** | On | On | ||||
| Total resistance | 2510 | 7000 | 3020 | 7000 | ||